These cables are suitable for fixed installation & able to serve power for residential and industrial Purpose. PVC insulated & sheathed multicore cables suitable for general purpose in Temperature range -15 C to 70 C.
Size | No of Wires & Dia. of Each Wire | Current Carrying Capacity | CR @ 20°C Ω/km |
||||
---|---|---|---|---|---|---|---|
In MM | In INCH | 2 Core Cable (Amp.) | 3/4 Core Cable (Amp.) | 2 Core Cable (Amp.) | 3/4 Core Cable (Amp.) | ||
2.5 Mm² | 1.78 | 0.070 | 16 | 14 | 19 | 17 | 12.10 |
4 Mm² | 2.25 | 0.088 | 21 | 19 | 26 | 23 | 7.41 |
6 Mm² | 2.76 | 0.108 | 27 | 24 | 32 | 28 | 4.61 |
10 Mm² | 3.56 | 0.140 | 37 | 32 | 42 | 37 | 4.05 |
16 Mm² | 4.51 | 0.177 | 50 | 44 | 58 | 52 | 1.91 |